Storm Drain & Stormwater Pipe Sizing Calculator

Enter design flow, slope and Manning’s n to screen 8–72 inch (200–1800 mm) storm drain pipes in cfs or L/s, with full-bore capacity and a velocity check.

Try a Common Scenario

Click to pre-fill the calculator with realistic values.

Enter your peak design flow, pipe slope, and Manning’s n to screen standard storm drain pipe sizes from 8–72 inches. Get the smallest diameter whose full-bore gravity capacity meets that flow, its capacity utilization and a self-cleansing velocity check. Starts in US units (cfs); the metric option screens 200–1800 mm pipes with the flow in L/s or m³/s.

How this stormwater pipe sizing screen works

Enter design flow Q, pipe slope S, and material roughness. The calculator selects the smallest screened standard RCP, HDPE, or CMP diameter whose full-bore Manning capacity meets Q. Then verify velocity, the governing minimum diameter, cover, and the connected system’s hydraulic grade line. This is gravity-flow screening, not a surcharged-network model.

Need Q first? Use the Rational Method calculator. This page sizes a pipe from a design flow; to go the other way and find what an existing diameter carries, full or at a known water depth, use the pipe capacity calculator. Culvert headwater and inlet/outlet control require a separate FHWA design check.

Input Parameters

Sizing Mode

cfs

Required: peak runoff at this pipe, not drainage area or rainfall intensity. Enter a positive flow in the displayed units.

Estimate design flow with the Rational Method

This screen compares Q with full-bore gravity capacity. It does not solve water depth, design-flow velocity, surcharge, or a connected network. For a culvert, check FHWA inlet and outlet control separately.

Pipe Properties

The calculator will screen standard 8–72 in diameters.
ft/ft

Enter slope as rise/run, not percent: 0.005 = 0.5% = 1:200. Supported range: 0.0001–1.

Self-cleansing check of the selected size. FHWA HEC-22 recommends at least 3 ft/s (0.9 m/s) flowing full; some agencies accept 2–2.5 ft/s (0.6–0.75 m/s).

Roughness Coefficient

Select a material to auto-fill Manning's n, or enter a custom value below

Typical values: 0.009-0.015 for smooth pipes, 0.022-0.030 for corrugated metal

Don't know this value? Look it up

For educational purposes only. Not a substitute for professional engineering judgment.

Interactive model

Interactive partial-flow storm drain hydraulics

Change pipe diameter, slope, roughness, and relative depth to see how wetted geometry controls Q/Qfull and V/Vfull.

Open full model (opens in a new tab)

How to size a storm drain pipe

Sizing a storm drain is a two-step problem: first work out how much water the pipe must carry, then find the smallest standard pipe that carries it at an acceptable velocity and slope.

  1. Find the design flow (Q). For most sites the peak stormwater flow comes from the Rational Method, Q = CiA, where C is the runoff coefficient, i is the rainfall intensity for your design storm and time of concentration, and A is the drainage area. In US units Q comes out in cubic feet per second (cfs); in metric, in m³/s or L/s. Use the Rational Method calculator to get Q.
  2. Set the pipe slope. Match the pipe to the available ground slope, or set a minimum self-cleansing slope (see below). Storm drains run by gravity, so slope drives both capacity and velocity.
  3. Check standard sizes against the design flow. Select “Size from design flow” and enter Q (cfs, L/s or m³/s), slope, and Manning’s n. The screen checks every standard size from 8–72 in (200–1800 mm), selects the smallest passing diameter and shows full-bore capacity Qfull, utilization and full-flow velocity. If even the largest size is too small, it says how many barrels in parallel would carry the flow. Allow capacity margin and apply your governing minimum diameter before choosing a design size.
  4. Verify the velocity. The calculator checks the selected size’s full-flow velocity against the minimum you choose: 3 ft/s (0.9 m/s) by default, per FHWA HEC-22, or 2.5 or 2 ft/s where your agency accepts it. Keep it below about 10 ft/s to limit abrasion. Then confirm the size against your local storm-sewer standard — many agencies set a minimum public storm drain of 12 or 15 inches regardless of the calculated capacity.

Manning’s equation for a circular pipe is Q = (1.486 / n) · A · R2/3 · S1/2 in US units (1.0 in place of 1.486 in SI), where A is the flow area, R is the hydraulic radius (R = D/4 for a full pipe) and S is the slope. The calculator on this page evaluates exactly this equation.

Storm drain pipe size chart (capacity by diameter)

Full-bore capacity (Qfull) and velocity for standard circular storm drain sizes from 8–72 in, computed from Manning’s equation with n = 0.013 (concrete / RCP) at three typical slopes. The paired metric sizes are for orientation; the metric chart below gives their own capacities. Capacity scales with √slope, so doubling the slope multiplies capacity by about 1.41.

Pipe dia. Paired metric Qfull @ 0.5% V @ 0.5% Qfull @ 1% V @ 1% Qfull @ 2% V @ 2%
8 in 200 mm 0.85 cfs 2.45 ft/s 1.21 cfs 3.46 ft/s 1.71 cfs 4.90 ft/s
10 in 250 mm 1.55 cfs 2.84 ft/s 2.19 cfs 4.02 ft/s 3.10 cfs 5.68 ft/s
12 in 300 mm 2.52 cfs 3.21 ft/s 3.56 cfs 4.54 ft/s 5.04 cfs 6.42 ft/s
15 in 375 mm 4.57 cfs 3.72 ft/s 6.46 cfs 5.26 ft/s 9.14 cfs 7.44 ft/s
18 in 450 mm 7.43 cfs 4.20 ft/s 10.5 cfs 5.94 ft/s 14.9 cfs 8.41 ft/s
21 in 525 mm 11.2 cfs 4.66 ft/s 15.8 cfs 6.59 ft/s 22.4 cfs 9.32 ft/s
24 in 600 mm 16.0 cfs 5.09 ft/s 22.6 cfs 7.20 ft/s 32.0 cfs 10.18 ft/s
30 in 750 mm 29.0 cfs 5.91 ft/s 41.0 cfs 8.36 ft/s 58.0 cfs 11.82 ft/s
36 in 900 mm 47.2 cfs 6.67 ft/s 66.7 cfs 9.44 ft/s 94.3 cfs 13.34 ft/s
42 in 1050 mm 71.1 cfs 7.39 ft/s 101 cfs 10.46 ft/s 142 cfs 14.79 ft/s
48 in 1200 mm 102 cfs 8.08 ft/s 144 cfs 11.43 ft/s 203 cfs 16.17 ft/s
54 in 1350 mm 139 cfs 8.74 ft/s 197 cfs 12.36 ft/s 278 cfs 17.49 ft/s
60 in 1500 mm 184 cfs 9.38 ft/s 260 cfs 13.26 ft/s 368 cfs 18.76 ft/s
66 in 1650 mm 237 cfs 9.99 ft/s 336 cfs 14.13 ft/s 475 cfs 19.99 ft/s
72 in 1800 mm 299 cfs 10.59 ft/s 424 cfs 14.98 ft/s 599 cfs 21.18 ft/s

Figures are full-flow (pipe flowing just full) and assume concrete/smooth-wall pipe at n = 0.013. Corrugated metal pipe (CMP, n ≈ 0.024) carries about 46% less at the same slope. Always confirm sizes and minimum diameters against your local storm-sewer design standard.

Metric pipe capacity chart (L/s)

Full-bore capacity in litres per second and velocity in m/s for standard 200–1800 mm pipes, n = 0.013, at the same three slopes. Use the calculator for your exact internal diameter.

Pipe dia. Qfull @ 0.5% V @ 0.5% Qfull @ 1% V @ 1% Qfull @ 2% V @ 2%
200 mm 23.2 L/s 0.74 m/s 32.8 L/s 1.04 m/s 46.4 L/s 1.48 m/s
250 mm 42.0 L/s 0.86 m/s 59.5 L/s 1.21 m/s 84.1 L/s 1.71 m/s
300 mm 68.4 L/s 0.97 m/s 96.7 L/s 1.37 m/s 137 L/s 1.93 m/s
375 mm 124 L/s 1.12 m/s 175 L/s 1.59 m/s 248 L/s 2.25 m/s
450 mm 202 L/s 1.27 m/s 285 L/s 1.79 m/s 403 L/s 2.54 m/s
525 mm 304 L/s 1.40 m/s 430 L/s 1.99 m/s 608 L/s 2.81 m/s
600 mm 434 L/s 1.54 m/s 614 L/s 2.17 m/s 868 L/s 3.07 m/s
750 mm 787 L/s 1.78 m/s 1,113 L/s 2.52 m/s 1,574 L/s 3.56 m/s
900 mm 1,280 L/s 2.01 m/s 1,810 L/s 2.85 m/s 2,560 L/s 4.02 m/s
1050 mm 1,931 L/s 2.23 m/s 2,731 L/s 3.15 m/s 3,862 L/s 4.46 m/s
1200 mm 2,757 L/s 2.44 m/s 3,899 L/s 3.45 m/s 5,514 L/s 4.88 m/s
1350 mm 3,774 L/s 2.64 m/s 5,337 L/s 3.73 m/s 7,548 L/s 5.27 m/s
1500 mm 4,998 L/s 2.83 m/s 7,069 L/s 4.00 m/s 9,997 L/s 5.66 m/s
1650 mm 6,445 L/s 3.01 m/s 9,114 L/s 4.26 m/s 12,890 L/s 6.03 m/s
1800 mm 8,128 L/s 3.19 m/s 11,495 L/s 4.52 m/s 16,256 L/s 6.39 m/s

Capacity by material and slope: RCP, HDPE, and CMP

The same nominal diameter can carry very different flow when its interior roughness changes. Values below are full-bore screening capacities in cfs; use the calculator for another n value or exact internal diameter.

Material Manning’s n Diameter 0.5%1%2%
RCP / concrete 0.013 8 in / ~200 mm 0.85 cfs1.21 cfs1.71 cfs
RCP / concrete 0.013 10 in / ~250 mm 1.55 cfs2.19 cfs3.10 cfs
RCP / concrete 0.013 12 in / ~300 mm 2.52 cfs3.56 cfs5.04 cfs
RCP / concrete 0.013 15 in / ~375 mm 4.57 cfs6.46 cfs9.14 cfs
RCP / concrete 0.013 18 in / ~450 mm 7.43 cfs10.5 cfs14.9 cfs
RCP / concrete 0.013 21 in / ~525 mm 11.2 cfs15.8 cfs22.4 cfs
RCP / concrete 0.013 24 in / ~600 mm 16.0 cfs22.6 cfs32.0 cfs
RCP / concrete 0.013 30 in / ~750 mm 29.0 cfs41.0 cfs58.0 cfs
RCP / concrete 0.013 36 in / ~900 mm 47.2 cfs66.7 cfs94.3 cfs
RCP / concrete 0.013 42 in / ~1050 mm 71.1 cfs101 cfs142 cfs
RCP / concrete 0.013 48 in / ~1200 mm 102 cfs144 cfs203 cfs
RCP / concrete 0.013 54 in / ~1350 mm 139 cfs197 cfs278 cfs
RCP / concrete 0.013 60 in / ~1500 mm 184 cfs260 cfs368 cfs
RCP / concrete 0.013 66 in / ~1650 mm 237 cfs336 cfs475 cfs
RCP / concrete 0.013 72 in / ~1800 mm 299 cfs424 cfs599 cfs
Smooth-interior HDPE 0.012 8 in / ~200 mm 0.93 cfs1.31 cfs1.85 cfs
Smooth-interior HDPE 0.012 10 in / ~250 mm 1.68 cfs2.37 cfs3.36 cfs
Smooth-interior HDPE 0.012 12 in / ~300 mm 2.73 cfs3.86 cfs5.46 cfs
Smooth-interior HDPE 0.012 15 in / ~375 mm 4.95 cfs7.00 cfs9.90 cfs
Smooth-interior HDPE 0.012 18 in / ~450 mm 8.05 cfs11.4 cfs16.1 cfs
Smooth-interior HDPE 0.012 21 in / ~525 mm 12.1 cfs17.2 cfs24.3 cfs
Smooth-interior HDPE 0.012 24 in / ~600 mm 17.3 cfs24.5 cfs34.7 cfs
Smooth-interior HDPE 0.012 30 in / ~750 mm 31.4 cfs44.4 cfs62.8 cfs
Smooth-interior HDPE 0.012 36 in / ~900 mm 51.1 cfs72.3 cfs102 cfs
Smooth-interior HDPE 0.012 42 in / ~1050 mm 77.1 cfs109 cfs154 cfs
Smooth-interior HDPE 0.012 48 in / ~1200 mm 110 cfs156 cfs220 cfs
Smooth-interior HDPE 0.012 54 in / ~1350 mm 151 cfs213 cfs301 cfs
Smooth-interior HDPE 0.012 60 in / ~1500 mm 200 cfs282 cfs399 cfs
Smooth-interior HDPE 0.012 66 in / ~1650 mm 257 cfs364 cfs514 cfs
Smooth-interior HDPE 0.012 72 in / ~1800 mm 324 cfs459 cfs649 cfs
Annular CMP 0.024 8 in / ~200 mm 0.46 cfs0.65 cfs0.93 cfs
Annular CMP 0.024 10 in / ~250 mm 0.84 cfs1.19 cfs1.68 cfs
Annular CMP 0.024 12 in / ~300 mm 1.36 cfs1.93 cfs2.73 cfs
Annular CMP 0.024 15 in / ~375 mm 2.47 cfs3.50 cfs4.95 cfs
Annular CMP 0.024 18 in / ~450 mm 4.02 cfs5.69 cfs8.05 cfs
Annular CMP 0.024 21 in / ~525 mm 6.07 cfs8.58 cfs12.1 cfs
Annular CMP 0.024 24 in / ~600 mm 8.66 cfs12.3 cfs17.3 cfs
Annular CMP 0.024 30 in / ~750 mm 15.7 cfs22.2 cfs31.4 cfs
Annular CMP 0.024 36 in / ~900 mm 25.5 cfs36.1 cfs51.1 cfs
Annular CMP 0.024 42 in / ~1050 mm 38.5 cfs54.5 cfs77.1 cfs
Annular CMP 0.024 48 in / ~1200 mm 55.0 cfs77.8 cfs110 cfs
Annular CMP 0.024 54 in / ~1350 mm 75.3 cfs107 cfs151 cfs
Annular CMP 0.024 60 in / ~1500 mm 99.8 cfs141 cfs200 cfs
Annular CMP 0.024 66 in / ~1650 mm 129 cfs182 cfs257 cfs
Annular CMP 0.024 72 in / ~1800 mm 162 cfs229 cfs324 cfs

RCP / concrete uses n = 0.013, Smooth-interior HDPE uses n = 0.012, Annular CMP uses n = 0.024, the typical values in the site’s Manning’s n table. Source basis: FHWA HEC-22. Material condition, joints, corrugation, and local design criteria can require another value.

Circular pipe partial-flow ratios: y/D, Q/Qfull, and V/Vfull

For a circular pipe at the same slope and Manning’s n, relative capacity depends only on relative depth. Discharge peaks at about 108% of full-flow capacity near y/D = 0.94, because hydraulic radius peaks before the water surface reaches the crown.

y/D A/Afull V/Vfull Q/Qfull
0.05 0.019 0.257 0.005
0.10 0.052 0.401 0.021
0.15 0.094 0.517 0.049
0.20 0.142 0.615 0.088
0.25 0.196 0.701 0.137
0.30 0.252 0.776 0.196
0.35 0.312 0.843 0.263
0.40 0.374 0.902 0.337
0.45 0.436 0.954 0.417
0.50 0.500 1.000 0.500
0.55 0.564 1.039 0.586
0.60 0.626 1.072 0.672
0.65 0.688 1.099 0.756
0.70 0.748 1.120 0.837
0.75 0.804 1.133 0.912
0.80 0.858 1.140 0.977
0.85 0.906 1.137 1.030
0.90 0.948 1.124 1.066
0.95 0.981 1.095 1.075
1.00 1.000 1.000 1.000

Geometry uses θ = 2 cos−1(1 − 2y/D), A = (D2/8)(θ − sinθ), P = Dθ/2, and R = A/P; Manning ratios then follow at fixed n and S. See Chow (1959) and FHWA HEC-22.

Where the design flow comes from: the Rational Method

A storm drain pipe is only as “right-sized” as the flow you size it for. For drainage areas up to roughly 200 acres, the Rational Method is the standard way to estimate the peak stormwater flow:

Q = C · i · A

  • C — runoff coefficient (from about 0.05 for flat sandy lawns up to 0.95 for asphalt or concrete pavement)
  • i — rainfall intensity for your design storm (often the 10-year storm for storm drains) at the time of concentration
  • A — contributing drainage area

In US units, with i in in/hr and A in acres, Q is in cfs after a unit factor of 1.008 (1 acre-inch per hour is almost exactly 1 cfs). In metric, with i in mm/h and A in hectares, Q = CiA / 360 in m³/s; multiply by 1,000 for L/s, which this calculator accepts directly. Compute Q in the Rational Method calculator, then bring it here and size the pipe so Qfull comfortably exceeds it.

Self-cleansing velocity & minimum slope

Minimum velocity (self-cleansing)

A storm drain should run fast enough to keep grit and sediment moving; slower than that, sediment settles and the pipe slowly clogs. FHWA HEC-22 recommends at least 3 ft/s (0.9 m/s) flowing full; some agencies accept 2–2.5 ft/s (0.6–0.75 m/s). The calculator checks the selected size against 3 ft/s by default, and you can pick 2.5 or 2 ft/s instead.

Maximum velocity (erosion)

Very high velocities scour pipe walls and damage joints. Keep full-flow velocity below roughly 10 ft/s (3 m/s) for normal materials (up to about 15 ft/s, 4.5 m/s, with abrasion-resistant pipe and energy dissipation at the outlet). The calculator warns above these thresholds.

Minimum slope follows from the minimum velocity: set the slope so the full pipe reaches it. The table gives that slope for each size at n = 0.013, flowing full, for each velocity the calculator offers. At HEC-22’s 3 ft/s, for example, a 12-inch pipe needs about 0.44% (1:229) and a 24-inch about 0.17% (1:576). Larger pipes self-cleanse at flatter slopes. Many jurisdictions also impose an absolute floor (commonly 0.5%) on small storm drains.

Minimum slope for the full-flow velocity shown, n = 0.013, pipe flowing full. Percent and 1-in-X.
Pipe dia. Slope for 2 ft/s full Slope for 2.5 ft/s full Slope for 3 ft/s full (HEC-22)
8 in 0.33% (1:300)0.52% (1:192)0.75% (1:133)
10 in 0.25% (1:403)0.39% (1:258)0.56% (1:179)
12 in 0.19% (1:514)0.30% (1:329)0.44% (1:229)
15 in 0.14% (1:693)0.23% (1:443)0.32% (1:308)
18 in 0.11% (1:883)0.18% (1:565)0.25% (1:393)
21 in 0.092% (1:1,080)0.14% (1:694)0.21% (1:482)
24 in 0.077% (1:1,300)0.12% (1:830)0.17% (1:576)
30 in 0.057% (1:1,750)0.090% (1:1,120)0.13% (1:776)
36 in 0.045% (1:2,230)0.070% (1:1,420)0.10% (1:989)
42 in 0.037% (1:2,730)0.057% (1:1,750)0.082% (1:1,220)
48 in 0.031% (1:3,270)0.048% (1:2,090)0.069% (1:1,450)
54 in 0.026% (1:3,820)0.041% (1:2,450)0.059% (1:1,700)
60 in 0.023% (1:4,400)0.036% (1:2,820)0.051% (1:1,950)
66 in 0.020% (1:4,990)0.031% (1:3,200)0.045% (1:2,220)
72 in 0.018% (1:5,610)0.028% (1:3,590)0.040% (1:2,490)

Velocity basis: FHWA HEC-22 (storm drains, flowing full). In metric the calculator applies 0.6 / 0.75 / 0.9 m/s to the exact metric size.

Worked examples

US units (cfs)

Size a storm drain for a 0.75-acre parking lot. Runoff coefficient C = 0.90 (asphalt), design rainfall intensity i = 4.0 in/hr, drainage area A = 0.75 acres.

  1. Design flow (Rational Method): Q = 1.008 × C · i · A = 1.008 × 0.90 × 4.0 × 0.75 = 2.72 cfs.
  2. Available slope: the run can be laid at S = 0.5% to match the site grade.
  3. Check a 12-inch pipe (concrete, n = 0.013) at 0.5%: full-bore capacity Qfull ≈ 2.52 cfs at V ≈ 3.21 ft/s. That is short of the 2.72 cfs design flow — undersized.
  4. Step up to a 15-inch pipe: Qfull ≈ 4.57 cfs at V ≈ 3.72 ft/s (60% utilization). Capacity now exceeds the design flow with margin, and the velocity is above HEC-22’s 3 ft/s self-cleansing minimum.
  5. Result: use a 15-inch storm drain at 0.5%. (A 12-inch pipe would carry the flow if the slope were steepened to about 0.58% — try it in the calculator.)

Metric (L/s)

Size a storm drain for a 1.8 ha commercial catchment. C = 0.90, i = 100 mm/h, pipe slope 1%, concrete pipe (n = 0.013).

  1. Design flow: Q = C · i · A / 360 = 0.450 m³/s = 450 L/s. Enter it in L/s, the calculator’s default metric unit.
  2. 525 mm carries 430 L/s flowing full — too small.
  3. 600 mm carries 614 L/s at 2.17 m/s (73% utilization), above the 0.9 m/s minimum. Use 600 mm.

These capacities are computed by the calculator above from Manning’s equation with A = πD²/4 and R = D/4.

Frequently asked questions

How do I size a storm drain pipe?

First estimate the peak design flow (Q) reaching the pipe, usually with the Rational Method, Q = CiA. Then use Manning’s equation to find the full-bore capacity of candidate pipe sizes at your available slope and pick the smallest standard size whose capacity comfortably exceeds Q. Finally check the full-flow velocity: FHWA HEC-22 recommends at least 3 ft/s (0.9 m/s) flowing full; some agencies accept 2–2.5 ft/s (0.6–0.75 m/s). Keep it below about 10 ft/s (3 m/s) for normal materials, and confirm the size against your local storm-sewer standards (many agencies set a minimum public storm drain of 12 or 15 inches).

What size storm drain pipe do I need?

It depends on the peak flow and the pipe slope, not just the area drained. As a rough guide for concrete or smooth-wall pipe at a 0.5% slope (n = 0.013), full-bore capacity is about 2.52 cfs for a 12-inch, 7.43 cfs for an 18-inch, 16.0 cfs for a 24-inch, 47.2 cfs for a 36-inch, 102 cfs for a 48-inch and 299 cfs for a 72-inch pipe. In metric, a 300 mm pipe carries about 68.4 L/s and a 600 mm pipe about 434 L/s at the same slope. Compute your design flow first, then choose the size whose capacity exceeds it with margin. The calculator on this page screens every standard size from 8–72 in (200–1800 mm) at your exact slope.

What is the minimum slope for a storm drain pipe?

The minimum slope is whatever keeps the flow fast enough to be self-cleansing. FHWA HEC-22 recommends at least 3 ft/s (0.9 m/s) flowing full; some agencies accept 2–2.5 ft/s (0.6–0.75 m/s). For n = 0.013 pipe flowing full, 3 ft/s needs about 0.75% (1:133) for an 8-inch, 0.44% (1:229) for a 12-inch and 0.17% (1:576) for a 24-inch pipe; at 2 ft/s the same pipes need 0.33%, 0.19% and 0.077%. Larger pipes self-cleanse at flatter slopes. Many agencies also set an absolute minimum, such as 0.5%, for small storm drains regardless of the velocity calculation.

What is the minimum velocity in a storm drain?

FHWA HEC-22 recommends at least 3 ft/s (0.9 m/s) flowing full; some agencies accept 2–2.5 ft/s (0.6–0.75 m/s). Below that, grit and sediment settle and the pipe gradually clogs; 2 ft/s (0.6 m/s) is also the common sanitary-sewer minimum. This calculator checks the selected pipe against 3 ft/s (0.9 m/s) by default, and you can choose 2.5 or 2 ft/s where your agency accepts it. When the selected size runs slower, it shows the slope that reaches your minimum.

Can I enter the design flow in litres per second (L/s)?

Yes. Switch to metric (SI): the design flow defaults to L/s, with m³/s as an option (1 m³/s = 1,000 L/s), and the calculator screens standard 200–1800 mm pipes. For example, 450 L/s at 1% with n = 0.013 needs a 600 mm pipe (614 L/s full-bore capacity); a 525 mm pipe carries only 430 L/s.

What if my design flow is more than a 72-inch pipe can carry?

The screen covers standard sizes up to 72 inches (1800 mm). Flowing full at 1% with n = 0.013, a 72-inch pipe carries about 424 cfs and an 1800 mm pipe about 11,495 L/s. Above that, the calculator says how many of the largest pipe you would need in parallel and the flow each barrel carries, and suggests a box section: compare box and circular sections with the culvert capacity calculator. Either way, check the hydraulic grade line of the whole system.

What Manning’s n should I use for storm drain pipe?

Use n = 0.013 for concrete (RCP) pipe with good joints; it is the standard design value and what the tables on this page assume, and a conservative value for smooth-wall HDPE or PVC (HDPE with a smooth interior is listed at 0.012). Corrugated metal pipe (CMP) is much rougher, around n = 0.024, so it carries about 46% less flow at the same size and slope. Always match Manning’s n to your actual pipe material.

Can this calculator size both storm sewers and culverts?

It sizes storm-sewer pipes by full-bore gravity capacity using Manning’s equation. For culverts, that calculation is only a screening check of barrel capacity and the friction side of outlet control; inlet control and headwater require a separate FHWA HDS-5 evaluation using the inlet geometry and headwater conditions. It also does not model pressurized (surcharged) storm-sewer flow. Use the dedicated culvert tools for culvert-specific checks.

Why is my storm drain pipe flowing more than 80% full?

Storm drains are usually designed to flow full or just under full at the peak design storm, but flowing consistently above about 80% leaves little margin and risks surcharging (pressurized flow) if the storm exceeds the design event. If the calculator shows a high depth ratio, step up to the next standard pipe size or increase the slope to add capacity headroom.

Related calculators